Hunter Industries MINI-CLIK-NO Installation Card Page: 1

MINI-CLIK
®
RAIN SENSOR
INSTALLATION CARD
Introduction
In most installations, the Mini-Clik sensor acts as a switch that breaks
the circuit to an irrigation system's solenoid valves in response to rain.
This allows the timer to advance as scheduled, but keeps the valves from
opening the water ow. Once the Mini-Clik has dried suciently, the switch
closes again to allow normal operation.
The Mini-Clik has 25' (8 m) of cable attached to it. The cable terminates
with blue leads. These leads will be wired to the SEN terminals or SEN and
SEN COM terminals of the controller. The order in which they are wired
does not matter (Figure 1). Remove the jumper from the two SEN terminals.
Note: For Hydrawise
®
controllers, you must complete the installation by
conguring the sensor in your Hydrawise account.
For the conduit model, Mini-Clik-C: This rain sensor unit is the same as the
standard model, except there is no aluminum mounting bracket and a ⁄"
threaded cap that allows for electrical conduit to totally enclose the wires
has been added. Unless local code states otherwise, plumbing-grade PVC
pipe can be used, as well as electrical-grade conduit.
Mounting
Standard Model
Using the screws provided, mount the
Mini-Clik on any surface where it will be
exposed to unobstructed rainfall, but not in
the path of sprinkler spray. The switch-housing
portion must be upright (Figure 2), but the
swivel bracket can be moved for mounting on
any angled surface. Loosen the locknut and
screw before swiveling the bracket, and then
re-tighten.
For model Mini-Clik-C: The conduit acts as the
mounting support for the unit. Therefore, place
and mount the conduit to allow for the desired
sensor location as described in the main instructions for the standard
model. Be sure to support the conduit suciently along its various lengths.
Helpful Hints for Mounting
A. When looking for a suitable location (such as on the side of a building
or post), the closer the Mini-Clik is to the controller, the shorter the
wire run will be. This will minimize the chance for wire breaks.
B. The ideal location for mounting is not always the most practical
location. In the case where a compromise must exist (such as a low
location on a side wall rather than a preferred higher location), note
that the Mini-Clik will still work because it will always receive some
rainfall — it just will not be as accurate in its gauging as it could be.
C. As described in the “Operation” section of this manual, “reset
rate” refers to the amount of time it takes the Mini-Clik to dry
out suciently for the sprinkler system to be allowed to come
back on. The mounting location will aect this rate and must
be taken into consideration should extreme conditions exist.
For example, mounting the Mini-Clik on a very sunny, southern end
of a building may cause the Mini-Clik to dry out sooner than desired.
Similarly, mounting on the northern end of a building with constant
shade may keep the Mini-Clik from drying soon enough.
Once the Mini-Clik is mounted, run the wire to the controller. Fasten it
every few feet with wire clips or staples for best results. If an extension
to the wire provided is needed, use the following table to determine the
minimum wire gauge needed:
If the extension needed is:
use:
X2
TM
or X-CORE
®
PRO-C
®
or HPC
HCC
HC
PRO-HC
ACC2
Figure 1
Figure 2
ACCI-CORE
®
24VAC
SEN
REM
C
24 VAC
24 VAC
GND
SEN-1
SEN COM
SEN-2
S1 S1
S2
S2
C
GND
AC1
AC2
REM
C
P/MV
SEN
SEN
AC2
AC1
GND
+
+
+
+
24
SEN1
SEN1
SEN2
SEN2
SEN3
SEN3
SEN4
SEN4
VAC
COM
TEST
SEN
SEN
REM
24VAC
24VAC
GND
ICC2
24V
24V
SENSOR 1
SENSOR 2
COMMON
SEN C
SEN 2
SEN 1
REM
24VAC
24VAC
GND
24VAC
COM
P/MV3
COM
+ SEN1 SEN1
+ SEN2
SEN2
+ SEN3
SEN3
0–100' (15–30 m)
18 AWG (1 mm)
>100' (>30 m)
16 AWG (1.3 mm)
24-Volt Solenoid Valves Only
(No Booster Pump) — Figure 3
With the two wires from the
Mini-Clik at the controller,
locate the “common ground”
wire of the solenoid valves. If
it is connected to the common
terminal on the controller,
disconnect it. Attach one
wire of the Mini-Clik to the
“common” terminal (usually
marked “C”) on the controller.
Attach the other wire of the
Mini-Clik to the common wire
leading to the valves.
1234
Mini-Clik
Controller
C
Figure 3
Solenoid
Valves
Common Wire to
All Valves
Figure 3
Mini-Clik
Controller
Common Wire to
All Valves
Valves
Solenoid
Note: The common wire to the valves does not have to be interrupted at
the controller. The Mini-Clik can be wired anywhere along the common
wire line (an example would be at the valve box location).